Guangzhou Hiseer Air Conditioning Co.,Ltd

Guangzhou Hiseer Air Conditioning Co.,Ltd Begin your green life with HISEER high efficiency heat pumps, reduce your carbon emissions, enhance your comfort and improve lives.

Manufacturer from China
Active Member
14 Years
Home / Products / Modular Ground Source Heat Pump /

Modular ground source electric heat pump efficiency

Contact Now
Guangzhou Hiseer Air Conditioning Co.,Ltd
City:guangzhou
Province/State:guangdong
Contact Person:Ms. Shelly Yan
Contact Now

Modular ground source electric heat pump efficiency

Ask Latest Price
Video Channel
Place of Origin :Guangzhou, China
Brand Name :HISEER
Model Number :GSWW60-DNNNE
Certification :CE, EN14511
MOQ :2 pieces
Packaging Details :plywood
Delivery Time :15-20 days after receiving payment
Payment Terms :TT or L/C at sight
Supply Ability :100 pieces / per day
Contact Now

Add to Cart

Find Similar Videos
View Product Description

Modular ground source electric heat pump efficiency

GSWW60-DNNNE, HISEER modular geothermal ground source heat pump, can be easily connected together for any size heating &

cooling system at the project spot. Maximum 64 units can be worked together for the largest 3840KW output capacity.

Geothermal ground source heat pump is a electrically powered system that takes advantage of the earth’s constant ground temperature to provide heating, cooling and hot water for your home or business.

Water to water system pumps heat through the use of a simple refrigeration system, it pumps heat from the warm earth in the winter and move it into your house or business. In the summer, the process is reversed. Since it costs far less to move heat than to make it, much less energy is consumed.

For closed loop system, water or an antifreeze solution is circulated through plastic pipes buried beneath the earth’s surface. During the winter the fluid collects heat from the earth and carries it through the system and placing it in the ground.

Open systems operate on the same principle as closed loop systems and can be installed where an adequate supply of suitable water is available and open discharges is feasible.

Loops can be installed three ways: horizontally, vertically or in a pond or lake. The type chosen depends on the available land area and the soil and rock type at the installation site.

GSWW60-DNNNE technical data

Modular Geothermal Heat Pump (heating only)

Heat pump

Type

GSWW60-DNNNE

Dimensions, weights, connection dimensions

Dimensions

HxWxD

1620x550X1250

Weight

kg

420

Refrigerant

Type

R407C

Filling weight

kg

10

Permissible operating pressure

Mpa

3

Pipe connector-hot side

Inch

G4”

Pipe connector-cold side

Inch

G4”

Evaporator

Type

Brazed plate heat exchanger

Condenser

Type

Brazed plate heat exchanger

Compressor

 

2xScroll

Performance Heat pump

Heat output

at B0/W35(1)

kW

60

Power consumption

kW

14.6

Performance factor

 

4.11

Hot side volume flow(3)

m3/h

10.4

Cold side volume flow(4)

m3/h

10.2

Heat output

at W10/W35(2)

kW

77

Power consumption

kW

14.9

Performance factor

 

5.17

Hot side volume flow

m3/h

13.4

Cold side volume flow

m3/h

13.6

Process medium

 

Brine made from water with 33Vol.% ethylene glycol

Power

Type

Triple phase

Sound power level

dB(A)

52

(1)B0/W35=Brine water inlet temperature 0℃, heating flow 35℃

(2)W10/W35=Well water inlet temperature 10℃, heating flow 35℃

(3)Heating flow for 5K temperature span

(4)Heat source flow for 4K temperature span

Inquiry Cart 0